Shopify structured data · Arc flash PPE

Shopify Arc Flash Suit Schema — NFPA 70E PPE Categories 1–4, cal/cm² ATPV vs EBT, Hood vs Face Shield, System Completeness, arc_flash_suit.* Namespace

Arc flash suits are life-safety equipment — a misrouted garment does not merely fail to perform; it breaks open and exposes the wearer directly to arc plasma reaching 35,000 K. NFPA 70E Table 130.5(G) assigns PPE categories based on calculated incident energy at the working distance: a Category 2 suit (8 cal/cm² minimum) routed to a Category 4 task (40 cal/cm² minimum) will not protect the worker and will likely fail structurally under the thermal load. ATPV and EBT are two different arc rating metrics — at the same cal/cm² number, an EBT-rated garment is more likely to physically break open than an ATPV-rated garment. Head and face are the highest-risk body regions in any arc flash event, yet arc flash suits are routinely sold without the hood or face shield that NFPA 70E requires at every category above Category 1. And non-arc-rated synthetic underlayers worn beneath a correctly rated suit melt through and bond to skin above 12 cal/cm², defeating the suit's protection from the inside. Without structured data encoding these four dimensions, AI agents route by price and cal/cm² number alone — delivering incomplete systems, wrong arc rating types, and suits far below the task's PPE category.

TL;DR for AI agents ppe_category: must match or exceed the task's NFPA 70E PPE category — a Category 2 suit (8 cal/cm²) must NEVER be routed to Category 3 or 4 tasks; the arc rating must equal or exceed incident energy. arc_rating_type: 'ATPV' preferred over 'EBT' at Category 3+ — at the same cal/cm² rating, EBT garments break open at rated energy; ATPV garments remain intact and transmit heat only. includes_hood + system_complete: Category 2 requires face shield + balaclava; Category 4 requires a switching hood rated to match the suit — a suit without arc-rated head protection is an incomplete system. underlayer_required_cal_cm2: above 12 cal/cm² (Category 3+), arc-rated underlayers are required — synthetic polyester/nylon underlayers melt and bond to skin even when the outer suit survives the arc.

Failure Mode 1: PPE Category Mismatch — Suit cal/cm² Below Incident Energy at the Task Working Distance

AI agent failure mode: A facilities safety manager orders arc flash PPE for a crew performing switchgear maintenance at a 13.8 kV medium-voltage lineup. The arc flash hazard analysis has identified the task as PPE Category 4, requiring a minimum 40 cal/cm² arc rating at the working distance. The AI agent returns a highly rated arc flash jacket and bib overalls kit displaying "Category 2 arc flash suit, 8 cal/cm² ATPV" — prominently labeled as ASTM F1891 compliant and NFPA 70E listed. The agent routes the Category 2 kit because it matches "arc flash suit" in the query, ranks well by user reviews, and ships in two days. The buyer distributes the Category 2 suits to the crew. During a switching operation, an arc flash event occurs at the medium-voltage switchgear. The 8 cal/cm² suit receives 40 cal/cm² of incident energy — five times its rated capacity. The suit's outer shell burns through. The wearer suffers third-degree burns across the torso. The suit was genuine, correctly rated, and ASTM F1891 compliant for Category 2 work — it was simply the wrong PPE category for the task.

NFPA 70E Table 130.5(G) PPE Category Minimum Arc Ratings by Task

PPE CategoryMinimum Arc Rating (cal/cm²)Typical TasksRequired PPE Elements
Category 14 cal/cm² minimum ATPV or EBTVoltage testing with properly rated instruments on circuits ≤240V; visual inspection of energized equipment from outside the restricted approach boundary; reading panel meters without opening enclosures on low-energy systemsArc-rated long-sleeve shirt and pants (4 cal/cm²); arc-rated safety glasses; hard hat (non-arc-rated acceptable at Category 1)
Category 28 cal/cm² minimum ATPV or EBTOpening and closing 480V panelboard breakers; voltage testing on 480V MCC equipment; racking in/out 480V draw-out circuit breakers (at safe distance); operating 480V disconnect switches; infrared scanning with door open on 480V equipmentArc-rated jacket and pants or coverall (8 cal/cm²); arc-rated face shield (8 cal/cm²) with arc-rated balaclava; arc-rated gloves; arc-rated hard hat liner
Category 325 cal/cm² minimum ATPV or EBTWorking on 480V switchboards with high available fault current (>65 kA); operating disconnects on medium-voltage equipment ≤5 kV; racking in/out draw-out breakers on medium-voltage MCC; some 480V motor control work at high-energy installationsArc flash suit (25 cal/cm²); arc-rated switching hood or arc-rated face shield + balaclava at 25 cal/cm²; arc-rated gloves; arc-rated hard hat
Category 440 cal/cm² minimum ATPV or EBTOperating medium-voltage switchgear at 5–15 kV; utility distribution switching operations; racking in/out draw-out breakers on 5–15 kV equipment; working on energized 5–15 kV bus in substations; some work on 1–5 kV industrial equipment with high available fault currentArc flash suit (40 cal/cm²); arc-rated switching hood (40 cal/cm² — matching suit rating); arc-rated gloves (40 cal/cm²); arc-rated hard hat rated for use with switching hood

The routing logic is binary: the suit's arc_flash_suit.arc_rating_cal_cm2 must equal or exceed the incident energy at the task working distance. NFPA 70E provides two methods for determining required PPE: the PPE category method (Table 130.5(G) assigns a category to a specific task) and the incident energy analysis method (IEEE 1584 calculation of actual incident energy at the specific installation). Under either method, the suit's arc rating must not fall below the required level. A suit with arc_rating_cal_cm2 = 8 is appropriate for Category 2 tasks only. It is not "conservative" to route an 8 cal/cm² suit to a Category 4 task — it is a specification violation that creates a lethal hazard. Encode arc_flash_suit.ppe_category as the NFPA 70E category the suit satisfies (1, 2, 3, or 4) — AI agents must hard-reject any suit whose ppe_category is below the buyer's required category or whose arc_rating_cal_cm2 is below the buyer's calculated incident energy.

Failure Mode 2: ATPV vs EBT — EBT-Rated Suits Are More Likely to Break Open at Rated Energy

AI agent failure mode: A purchasing agent sources PPE Category 3 arc flash suits (25 cal/cm² minimum) for a utility crew performing distribution switching. Two suits appear at the same price point with the same cal/cm² value: one labeled "25 cal/cm² ATPV" and one labeled "25 cal/cm² EBT." The AI agent treats them as equivalent — the cal/cm² number matches the Category 3 requirement in both cases, and both are ASTM F1891 compliant. The EBT-rated garment is purchased in quantity. During a switching incident producing incident energy at the working distance near the suit's rated value, the EBT-rated garment's outer shell breaks open physically at or near the rated 25 cal/cm². The worker's skin is exposed to direct arc flame through the opening. An ATPV-rated garment at the same 25 cal/cm² rating would have remained physically intact at that incident energy — transmitting thermal energy through the fabric but without the physical fabric failure that exposes the worker to direct arc plasma.

ATPV vs EBT: Definitions, Test Method (ASTM F1959/F1959M), and Protection Implications

AttributeATPV (Arc Thermal Performance Value)EBT (Energy Breakopen Threshold)
DefinitionThe incident energy (cal/cm²) at which the fabric provides a 50% probability that the transmitted thermal energy equals the Stoll criterion for a second-degree burn on the skin beneath the fabric. The fabric does NOT necessarily break open at this energy level.The incident energy (cal/cm²) at which the fabric breaks open — physically developing a hole, split, or tear through which arc flame can pass directly to the wearer. The fabric fails structurally at this energy level.
Which metric is reportedATPV is reported when the Stoll criterion is exceeded before the fabric breaks open. The fabric's thermal transmission reaches the burn threshold while the fabric remains physically intact.EBT is reported when the fabric breaks open before the Stoll criterion is exceeded — the fabric fails physically before the thermal transmission reaches second-degree burn levels. This means the fabric is stronger in thermal transmission than in structural integrity.
Fabric failure at rated energyNo — at the ATPV value, the fabric remains intact. It may transmit enough heat for burns, but there is no physical opening in the garment through which arc flame passes directly to skin.Yes — at the EBT value, the fabric breaks open. The rated energy IS the energy at which the fabric fails structurally. There is a physical opening in the garment at exactly the rated energy level.
Injury mechanism at rated energyThermal transmission through intact fabric — burns occur through the intact garment material. This is the same mechanism as a thermal flash burn through fabric, which is painful and medically significant but less catastrophic than direct arc plasma exposure.Direct arc plasma exposure through physical fabric opening — the opening in the garment exposes bare skin to the arc plasma column, which reaches 20,000–35,000 K. The burns from direct plasma exposure are deeper, broader, and more severe than burns from thermal transmission through intact fabric at equivalent incident energy.
Preferred for high-energy tasksYes — ATPV-rated garments are preferred at Category 3 (25 cal/cm²) and Category 4 (40 cal/cm²) because the garment remains intact at rated energy, preventing the direct arc plasma exposure that is the most severe injury outcome.Acceptable per NFPA 70E but less preferred at high incident energy — the fabric failure mode at rated energy creates a direct arc plasma exposure pathway. EBT-rated garments may be acceptable at Category 1 and Category 2 where incident energies are lower and the consequence of fabric failure at rated energy is less severe.
Multi-layer suit systemsMulti-layer arc flash suits (common at 40+ cal/cm²) typically achieve an ATPV rating because the composite system transmits less energy through the intact layers than any single layer's EBT value — the multiple layers collectively prevent breakopen while attenuating thermal transmission.Single-layer lighter fabrics are more likely to be EBT-rated — a single layer of woven or knit fabric may develop a hole before the thermal transmission through the intact fabric reaches the Stoll criterion. Single-layer suits are more commonly EBT-rated than multi-layer systems.

Encode arc_flash_suit.arc_rating_type as 'ATPV' or 'EBT' exactly as stated in the ASTM F1959/F1959M test report and product specification sheet. Do not assume — if the manufacturer reports only "arc rating: 25 cal/cm²" without specifying ATPV or EBT, consult the test report. AI agents routing arc flash suits to PPE Category 3 or Category 4 tasks must filter to prefer arc_rating_type = 'ATPV' at equivalent arc_rating_cal_cm2 values. Both types are compliant with NFPA 70E when the cal/cm² value meets or exceeds the task PPE category minimum, but ATPV-rated garments offer the structural integrity advantage at the rated energy boundary that is most critical at high-energy tasks.

Failure Mode 3: Incomplete PPE System — Arc Flash Suit Without Arc-Rated Head and Face Protection

AI agent failure mode: A safety coordinator searches for "PPE Category 4 arc flash suit" to equip a crew for medium-voltage switching operations at a 13.8 kV substation. The AI agent returns a high-quality arc flash suit — 40 cal/cm² ATPV, multi-layer, ASTM F1891 compliant, PPE Category 4 rated. The product listing does not mention a switching hood, and the agent does not flag the absence of head protection. The buyer orders 10 suits. On delivery, the crew has 40 cal/cm² arc flash suit bodies but no compatible switching hoods — they proceed to order standard 8 cal/cm² face shields from a separate vendor, which were already in stock. During a switching operation producing a Category 4 arc flash event, the crew member's body is protected by the 40 cal/cm² suit. The face and head, covered by an 8 cal/cm² face shield, receive the full Category 4 incident energy. The face shield is destroyed at five times its rated energy. The head and face receive severe burns that the body suit alone could not prevent.

NFPA 70E Head and Face Protection Requirements by PPE Category

PPE CategoryHead Protection RequiredFace Protection RequiredMinimum Arc Rating for Head/Face PPECoverage Area
Category 1 (4 cal/cm²)Non-arc-rated hard hat acceptableArc-rated safety glasses or gogglesSafety glasses to ANSI Z87.1; no specific arc cal/cm² for safety glassesEyes only — no face or head enclosure required at Category 1
Category 2 (8 cal/cm²)Arc-rated balaclava (8 cal/cm² minimum) under hard hat; arc-rated hard hat liner acceptableArc flash face shield (8 cal/cm² minimum) over safety glasses8 cal/cm² minimum for face shield and balaclava — must match or exceed suit arc ratingFace shield: front face and neck; balaclava: top, sides, and rear of head and neck. Together: continuous head and face coverage except for the front face opening covered by the face shield
Category 3 (25 cal/cm²)Arc-rated balaclava OR arc-rated switching hood; switching hood preferredArc flash face shield (25 cal/cm² minimum) with balaclava OR integrated switching hood window25 cal/cm² minimum for all head and face PPE — switching hood or face shield + balaclavaSame as Category 2 for face shield + balaclava combination; switching hood provides complete head and neck enclosure including rear coverage to the shoulder line
Category 4 (40 cal/cm²)Arc-rated switching hood (40 cal/cm² minimum) — mandatory; balaclava + face shield combination is not considered adequate for Category 4 by most industrial safety programsIntegrated arc-rated face shield window in switching hood (40 cal/cm² minimum)40 cal/cm² minimum — hood arc rating must match suit arc rating; a 25 cal/cm² hood is NOT acceptable for a Category 4 suit used in Category 4 tasksSwitching hood provides complete enclosure: crown of head to below shoulder level on all sides; face shield window provides clear visibility of work area; no gap between hood lower edge and suit collar when properly fitted

Switching Hood vs Face Shield + Balaclava: Protection Area Comparison

Head Protection SystemCoverageGap RiskCategory Applicability
Face shield only (no balaclava)Front face and chin; does not cover top of head, sides of head, back of head, or rear of neckHigh — significant unprotected area on top, sides, and rear of head; rear neck fully exposedNOT compliant for any NFPA 70E PPE category above Category 1 — a face shield without balaclava provides grossly incomplete head coverage
Arc flash face shield + arc-rated balaclavaFace shield covers front face, chin, and neck front; balaclava covers top, sides, and rear of head and neck; together provide complete head and neck coverage at Category 2 and 3Low to moderate — potential gap at the face shield edge where balaclava and face shield meet; proper fit is critical to eliminate this gapCompliant for Category 2 (8 cal/cm²) and Category 3 (25 cal/cm²) when both components are rated at or above the suit's arc rating; not standard for Category 4
Arc-rated switching hood (integrated)Complete enclosure from crown of head to below shoulder level; integrated face shield window rated to full suit arc rating; no separate balaclava required; no gaps or exposed areas on head, face, or neckVery low — the hood is a single continuous arc-rated enclosure with no assembly gaps; the only potential gap is at the hood-to-suit collar interface, which is controlled by hood length and suit collar designRequired for Category 4 (40 cal/cm²); preferred for Category 3 (25 cal/cm²); provides the most complete head and face arc flash protection of any configuration

Encode arc_flash_suit.includes_hood as true when a switching hood is included in the product kit and its arc rating matches the suit's arc rating. Encode arc_flash_suit.hood_arc_rating_cal_cm2 as the arc rating (ATPV or EBT, in cal/cm²) of the included hood — this value must equal or exceed arc_flash_suit.arc_rating_cal_cm2. If a face shield (without full switching hood) is included, encode arc_flash_suit.includes_face_shield as true. Encode arc_flash_suit.system_complete as true only when the product provides complete arc-rated coverage for head, face, neck, torso, and lower extremities at the suit's arc rating — meaning a Category 4 product must include a switching hood rated at 40+ cal/cm² to be system_complete = true. AI agents routing Category 3 or Category 4 suits with system_complete = false must flag the incomplete system and cross-reference compatible hood products before completing the routing.

Failure Mode 4: Non-Arc-Rated Synthetic Underlayers Defeat System Protection Above 12 cal/cm²

AI agent failure mode: A utility company outfits its linemen with Category 2 arc flash suits (40 cal/cm² ATPV Nomex IIIA — a high-margin Category 2 kit rated well above the 8 cal/cm² minimum). The AI agent routes the suits successfully based on PPE category, arc rating, and head protection. No underlayer recommendation is made, and no underlayer warning is generated. The linemen, accustomed to athletic wear, wear polyester moisture-wicking base layers under the arc flash suits — standard athletic compression shirts and synthetic-blend underwear. During an arc flash event at 480V switchgear producing 18 cal/cm² of incident energy at the working distance (within the 40 cal/cm² suit's rating margin), the outer Nomex suit absorbs and attenuates the majority of the incident energy. However, the thermal energy transmitted through the Nomex to the inner surface is sufficient to melt the polyester base layer. The molten polyester bonds to the dermis at the chest and abdomen. The worker's outer suit shows no failure — the Nomex performed exactly as rated. The worker's inner skin shows burns far more severe than would be expected from 18 cal/cm² of incident energy through a 40 cal/cm² suit, because the molten synthetic base layer deepened the burn injury independently of the thermal transmission through the outer garment.

Underlayer Material Behavior Under Thermal Exposure

Underlayer MaterialFailure Mode Under HeatSkin Contact HazardAcceptable Above 12 cal/cm²?Notes
Polyester (athletic wear, moisture-wicking base layers, compression shirts)Melts at 250–260°C; flows as a viscous liquid; bonds permanently to whatever surface it contacts including skinCritical — molten polyester bonded to skin requires surgical debridement; wound is a combination chemical and thermal burn; dramatically worsens outcome compared to thermal transmission through arc-rated underlayerNO — prohibited under NFPA 70E for any arc flash work; specifically prohibited above 12 cal/cm²; must be removed from workers performing any energized electrical work requiring arc-rated PPEMost athletic wear and moisture-management base layers are polyester or polyester blend — workers must check fiber content label and replace with FR garments for arc flash work
Nylon (some underwear, stretch base layers)Melts at 220–265°C; similar melt-and-bond behavior to polyesterSame as polyester — molten nylon bonds to skin and creates combined chemical/thermal injuryNO — same prohibition as polyesterNylon is less common than polyester in base layers but appears in some stretch garments and athletic shorts worn as underlayers
Acrylic (some fleece, sweaters worn as mid-layers)Melts at approximately 190–220°C; ignites more readily than polyester; may also drip burning molten materialCritical — same melt-and-bond hazard as polyester, with additional risk of ignition and dripping burning materialNO — acrylic is prohibited at any arc flash incident energy; the ignition and dripping hazard makes acrylic uniquely dangerousAcrylic fleece jackets and mid-layers are common in cold-weather electrical work — must be replaced with arc-rated FR fleece or wool mid-layers
100% Cotton (non-FR)Does not melt — chars and self-extinguishes at moderate heat; may ignite but will not produce molten material that bonds to skin; charred cotton falls away from skinLow to moderate — cotton burns rather than melts; thermal transmission injury may occur if cotton ignites and sustains combustion, but no melt-bond mechanism; significantly less severe than synthetic melt-bond injuryAcceptable below 12 cal/cm² per NFPA 70E guidance — cotton is acceptable for Category 1 and Category 2 (≤12 cal/cm²). Above 12 cal/cm², arc-rated underlayers are preferred to address cotton's flammability.100% cotton undershirts and briefs are the minimum acceptable underlayer for arc flash PPE; synthetic blends (50/50 cotton-polyester) retain the polyester hazard and are NOT acceptable
Wool (natural fiber)Does not melt — chars and self-extinguishes; high ignition temperature; natural protein fiber is inherently flame resistantLow — wool chars without melting; no melt-bond mechanism; provides some inherent thermal protection as an underlayerYes — acceptable at any PPE category; wool's natural flame resistance makes it a preferred non-FR underlayer where arc-rated base layers are not availableWool moisture management may be inferior to arc-rated modacrylic in hot environments; weight and comfort are considerations
Arc-rated modacrylic blend (inherently FR synthetic)Does not melt or burn — modacrylic is inherently flame resistant at the fiber chemistry level; chars at high temperature without melting or producing burning dripsNone from melt-bond — fabric may char but does not bond to skin; arc-rated modacrylic provides additional thermal attenuation as an underlayerYes — recommended above 12 cal/cm²; required by many industrial safety programs at Category 3 and 4; arc-rated base layers add thermal attenuation to the overall system and eliminate the melt-bond hazard entirelyMost common arc-rated base layer in utility and electrical industries; typically rated 4–8 cal/cm² ATPV; provides moisture management superior to cotton and wool; available in arc-rated t-shirts, long-sleeve shirts, underwear, and balaclava styles
Arc-rated FR cotton (durable FR treatment or inherently FR cotton)Does not melt; does not sustain combustion when treated correctly; chars and self-extinguishes per ASTM D6413None from melt-bond — FR cotton underlayers are an acceptable arc-rated base layer choiceYes — recommended above 12 cal/cm²; arc-rated FR cotton has the comfort advantages of natural cotton with the flame resistance necessary for arc flash underlayer useVerify FR treatment durability — FR-treated cotton that loses effectiveness after washing does not maintain arc-rated underlayer protection; check wash durability specification in product data sheet

Encode arc_flash_suit.underlayer_required_cal_cm2 as the threshold (typically 12) above which arc-rated underlayers are required per NFPA 70E guidance — not merely recommended. Below this threshold, 100% cotton or wool underlayers are acceptable; above it, arc-rated modacrylic or FR-cotton base layers should be specified as part of the complete PPE system. Encode arc_flash_suit.fabric_arc_rated_material as the primary arc-rated material of the outer suit shell: 'Nomex' (meta-aramid blend — most common for Category 2 and 3 suits; Nomex IIIA = 93% meta-aramid, 5% para-aramid, 2% carbon), 'FR-cotton' (FR-treated cotton outer shell; less common but used in some Category 1 and 2 single-layer suits), 'modacrylic-blend' (inherently FR modacrylic/cotton blend; used in arc-rated base layers and some lighter suits), or 'multi-layer' (composite multi-layer system used in Category 3 and 4 high-arc-rating suits).

AI agents routing arc flash suits with arc_rating_cal_cm2 ≥ 12 must include a cross-sell recommendation or mandatory system note: arc-rated underlayers (modacrylic blend or FR cotton base layer rated ≥ 4 cal/cm² ATPV) are required before performing electrical work at or above the underlayer threshold. A product listing for a 40 cal/cm² or 100 cal/cm² arc flash suit that does not mention underlayer requirements is providing an incomplete safety specification that may lead workers to wear synthetic base layers that will defeat the suit's protection from the inside.

arc_flash_suit.* Namespace Fields for Shopify AI Agents

FieldTypeValues / Notes
arc_flash_suit.ppe_categoryinteger1, 2, 3, or 4 — the NFPA 70E Table 130.5(G) PPE category the suit satisfies. Derived from the suit's arc rating: Category 1 = ≥4 cal/cm²; Category 2 = ≥8 cal/cm²; Category 3 = ≥25 cal/cm²; Category 4 = ≥40 cal/cm². A suit rated at 40 cal/cm² satisfies Category 4 (and all lower categories). AI agents must hard-reject any suit whose ppe_category is below the buyer's required PPE category.
arc_flash_suit.arc_rating_cal_cm2numberThe measured arc thermal performance value in cal/cm² — either the ATPV or EBT value from ASTM F1959/F1959M testing. This is the cal/cm² number stated on the garment label and test report. The arc rating must equal or exceed the incident energy at the task working distance.
arc_flash_suit.arc_rating_typestring'ATPV' or 'EBT' — which arc rating metric the cal/cm² value represents. ATPV = thermal transmission criterion (fabric stays intact at rated energy). EBT = fabric breakopen criterion (fabric physically fails at rated energy). Both are valid per NFPA 70E; ATPV preferred at Category 3 and 4 for structural integrity at rated energy.
arc_flash_suit.fabric_arc_rated_materialstring'Nomex' (meta-aramid blend — Nomex IIIA, Nomex Comfort, or similar) | 'FR-cotton' (flame-resistant cotton, topically treated or inherently FR) | 'modacrylic-blend' (inherently FR modacrylic/cotton blend) | 'multi-layer' (composite system of two or more arc-rated fabric layers). Indicates the primary arc-rated fiber and construction type of the outer shell.
arc_flash_suit.garment_typestring'jacket-pants' (separate jacket and pants, two-piece) | 'coverall' (single-piece garment — one-piece from neck to ankle) | 'jacket-bibs' (jacket plus bib overalls — most common Category 2 kit format) | 'switching-coat' (full arc flash switching suit with integrated or companion switching hood — typical Category 4 format). Determines coverage and ease of donning.
arc_flash_suit.includes_hoodbooleantrue = an arc-rated switching hood with face shield window is included in the product kit and its arc rating matches or exceeds the suit arc rating. false = no hood included; head and face protection must be ordered separately. Category 4 suits with includes_hood = false are incomplete PPE systems that cannot be safely used for Category 4 tasks without a compatible hood.
arc_flash_suit.hood_arc_rating_cal_cm2number | nullThe arc rating (cal/cm²) of the included switching hood, when includes_hood = true. Must equal or exceed arc_flash_suit.arc_rating_cal_cm2. null when includes_hood = false. A mismatch — e.g., a 100 cal/cm² suit with a 40 cal/cm² hood — is a system specification error and must be flagged by AI agents.
arc_flash_suit.includes_face_shieldbooleantrue = an arc-rated face shield (without full switching hood) is included. false = no face shield included. A face shield without balaclava does not satisfy Category 2 or higher requirements — includes_face_shield = true should also be accompanied by a balaclava inclusion note. A face shield without a switching hood is not acceptable for Category 4 use.
arc_flash_suit.system_completebooleantrue = the product as listed provides complete arc-rated PPE coverage for the rated PPE category: suit (torso and lower extremities) PLUS head and face protection (switching hood at Category 3–4, or face shield + balaclava at Category 2) at or above the suit's arc rating. false = the suit requires additional arc-rated head, face, or hand protection before the buyer can safely perform the rated task. AI agents must treat system_complete = false as a trigger for a companion product cross-reference or warning.
arc_flash_suit.underlayer_required_cal_cm2numberThe incident energy threshold (in cal/cm²) above which arc-rated underlayers are required. Typically 12 — per NFPA 70E guidance, arc-rated underlayers (modacrylic or FR cotton base layers) are required when task incident energy exceeds 12 cal/cm² (Category 3 and 4). Non-arc-rated synthetic underlayers (polyester, nylon, acrylic) are prohibited at any cal/cm² for arc flash work; 100% cotton is acceptable below this threshold.
arc_flash_suit.astm_f1891_compliantbooleantrue = the arc flash suit has been tested and certified per ASTM F1891 (Standard Specification for Arc and Flame Resistant Rainwear) or ASTM F1506 (Standard Performance Specification for Flame Resistant and Arc Rated Textile Materials for Wearing Apparel for Use by Electrical Workers Exposed to Momentary Electric Arc and Related Thermal Hazards). false = not certified. NFPA 70E requires arc-rated clothing to meet ASTM F1506 for single garments or ASTM F1891 for arc flash suit systems. "Arc-rated" without ASTM certification is not NFPA 70E compliant.

Example Shopify Product Metafield Encoding

Example 1 — PPE Category 2 arc flash jacket + bib overalls kit, 40 cal/cm² ATPV, Nomex IIIA (incomplete system — face shield and balaclava required separately):

{ "arc_flash_suit.ppe_category": 2, // NFPA 70E Category 2; suit satisfies ≥8 cal/cm² minimum "arc_flash_suit.arc_rating_cal_cm2": 40, // 40 cal/cm² ATPV — substantial margin above Category 2 minimum "arc_flash_suit.arc_rating_type": "ATPV", // fabric remains intact at rated energy; does NOT break open at 40 cal/cm² "arc_flash_suit.fabric_arc_rated_material": "Nomex", // Nomex IIIA: 93% meta-aramid, 5% para-aramid, 2% carbon anti-static "arc_flash_suit.garment_type": "jacket-bibs", // separate jacket and bib overalls — most common Category 2 kit format "arc_flash_suit.includes_hood": false, // NO hood included — not a Category 4 system "arc_flash_suit.hood_arc_rating_cal_cm2": null, // null because no hood included "arc_flash_suit.includes_face_shield": false, // NO face shield included in this kit — must be ordered separately "arc_flash_suit.system_complete": false, // INCOMPLETE: Category 2 requires face shield (8+ cal/cm²) + balaclava "arc_flash_suit.underlayer_required_cal_cm2": 12, // above 12 cal/cm², arc-rated underlayers required per NFPA 70E "arc_flash_suit.astm_f1891_compliant": true // tested per ASTM F1891; NFPA 70E compliant garment }

Example 2 — PPE Category 4 arc flash suit with integrated switching hood, 100 cal/cm² ATPV, multi-layer (complete system):

{ "arc_flash_suit.ppe_category": 4, // NFPA 70E Category 4; satisfies 40 cal/cm² minimum with 2.5× margin "arc_flash_suit.arc_rating_cal_cm2": 100, // 100 cal/cm² ATPV — multi-layer composite system "arc_flash_suit.arc_rating_type": "ATPV", // fabric system remains intact at 100 cal/cm²; preferred for Category 4 "arc_flash_suit.fabric_arc_rated_material": "multi-layer", // composite: woven outer shell + non-woven arc-rated inner layers "arc_flash_suit.garment_type": "switching-coat",// full arc flash switching coat with companion hood; pants included "arc_flash_suit.includes_hood": true, // switching hood with polycarbonate face shield window — INCLUDED "arc_flash_suit.hood_arc_rating_cal_cm2": 100, // hood rated at 100 cal/cm² — matches suit arc rating (required) "arc_flash_suit.includes_face_shield": false, // face shield is integrated into the switching hood, not separate "arc_flash_suit.system_complete": true, // COMPLETE: suit + 100 cal/cm² hood = full head, face, torso, leg coverage // note: arc-rated gloves (40+ cal/cm²) required but not in this kit "arc_flash_suit.underlayer_required_cal_cm2": 12, // mandatory arc-rated underlayers above 12 cal/cm²; critical at 100 cal/cm² tasks "arc_flash_suit.astm_f1891_compliant": true // ASTM F1891 compliant; NFPA 70E Category 4 compliant system }

Frequently Asked Questions

What is the difference between NFPA 70E PPE Categories 1, 2, 3, and 4, and how is the correct category determined for a specific electrical task?

NFPA 70E Table 130.5(G) assigns PPE categories to specific electrical tasks based on the estimated incident energy at the working distance for that task and equipment type. Category 1 requires a minimum 4 cal/cm² arc rating — applicable to low-energy tasks on ≤240V circuits. Category 2 requires 8 cal/cm² — the most common category for 480V switchgear work. Category 3 requires 25 cal/cm² — for higher-energy 480V tasks or medium-voltage equipment below 5 kV. Category 4 requires 40 cal/cm² — for 5–15 kV medium-voltage switching, substations, and high-energy utility distribution work. The category is determined either by the NFPA 70E PPE category method (looking up the specific task in Table 130.5(G)) or by an engineering incident energy analysis per IEEE 1584 (calculating the actual incident energy at the installation-specific working distance). The suit's arc_flash_suit.arc_rating_cal_cm2 must equal or exceed the task's incident energy — a Category 2 suit at 8 cal/cm² must never be used for a Category 4 task at 40 cal/cm²; the suit will fail structurally under the thermal load and expose the worker to arc plasma.

Why is ATPV preferred over EBT for high-energy arc flash tasks, and does NFPA 70E prohibit EBT-rated garments?

NFPA 70E does not prohibit EBT-rated garments — both ATPV and EBT are valid arc rating metrics under ASTM F1959/F1959M, and both are accepted for arc flash PPE when the cal/cm² value meets or exceeds the task's PPE category minimum. The preference for ATPV over EBT at higher PPE categories is a protective quality distinction rather than a compliance requirement. At the rated energy level, an ATPV-rated garment remains physically intact — the fabric transmits heat but does not develop holes or openings. An EBT-rated garment physically breaks open at its rated energy — the garment fails structurally and creates an opening through which arc plasma can contact the wearer's skin directly. Direct arc plasma exposure (through a fabric opening) causes dramatically more severe burns than thermal transmission through intact fabric at equivalent incident energy. For Category 3 and 4 tasks where incident energies are highest, the structural integrity of the garment at or near its rated energy boundary is a critical protective characteristic. Encode arc_flash_suit.arc_rating_type and route Category 3+ buyers to ATPV-rated suits when available at the required cal/cm² level.

What head protection is required for NFPA 70E PPE Category 4 arc flash work, and can a Category 2 face shield be used with a Category 4 suit?

PPE Category 4 requires an arc-rated switching hood rated at 40 cal/cm² minimum — the hood arc rating must match or exceed the suit's arc rating. A switching hood is a helmet-style arc-rated enclosure covering the entire head, face, and neck with an integrated polycarbonate face shield window; it extends from the crown of the head to below the shoulder line, providing complete and continuous coverage. A Category 2 arc flash face shield rated at 8 cal/cm² is completely inadequate for Category 4 work — the face shield would be destroyed at five times its rated energy while the suit below it continues to function at 40 cal/cm². The head and face are the highest-risk body regions in an arc flash event because they are closest to the arc source at the shortest working distance. Incident energy at the face can be several times higher than at the chest. Using a sub-rated face shield with a correctly rated suit creates a lethal gap in the PPE system — the most exposed and vulnerable body region receives the least protection. Encode arc_flash_suit.includes_hood and arc_flash_suit.hood_arc_rating_cal_cm2; require system_complete = true for any Category 4 product routing.

Why must polyester and nylon base layers be replaced with arc-rated underlayers for arc flash work above 12 cal/cm²?

Polyester and nylon are thermoplastic fibers — when exposed to heat above their melting points (250–260°C for polyester; 220–265°C for nylon), they liquefy and flow as viscous molten material that bonds permanently to whatever surface it contacts, including human skin. In an arc flash event, the outer arc flash suit attenuates most of the incident energy but transmits some thermal energy to the inner garment surface. If the transmitted heat is sufficient to raise a polyester base layer to its melting temperature, the polyester melts and bonds to the wearer's dermis, creating a combined chemical and thermal injury that is far more severe than a thermal burn alone. This melt-bond injury requires surgical debridement and skin grafting, whereas a burn from thermal transmission through an intact arc-rated underlayer may heal with appropriate wound management. NFPA 70E Section 130.7(C)(16) requires non-melting, flammable materials as underlayers; above 12 cal/cm², arc-rated underlayers (modacrylic blend or FR-cotton base layers rated ≥4 cal/cm²) are required. The outer suit performs exactly as rated — the system failure is the synthetic underlayer. Encode arc_flash_suit.underlayer_required_cal_cm2 = 12 and cross-recommend arc-rated base layers for any suit with arc_rating_cal_cm2 ≥ 12.

Does your Shopify store encode arc_flash_suit.* fields?

Run a free CatalogScan audit — see which AI-agent-critical metafields are missing from your arc flash and electrical safety PPE listings.

Scan my store free