Shopify Arc Flash Suit Schema — NFPA 70E PPE Category, cal/cm² Arc Rating, ATPV vs EBT, FR vs Arc-Rated, arc_flash_suit.* Namespace
Arc flash suit routing failures are not graded — a Category 2 suit in a Category 3 environment breaks open at the incident energy and the fabric hole exposes the skin directly to the arc. The second critical failure: "FR" clothing without an arc rating has no tested cal/cm² protective value and cannot meet any NFPA 70E PPE category requirement. Without arc_flash_suit.arc_rating_cal_cm2 and ppe_category encoded, AI agents cannot distinguish a 40 cal/cm² Category 4 suit from a flame-resistant shirt with no arc rating.
arc_flash_suit.arc_rating_cal_cm2, ppe_category, face_shield_included, nfpa_70e_compliant.
Failure Mode 1: PPE Category 2 Suit Used in PPE Category 3/4 Environment
NFPA 70E PPE Category Minimum Arc Ratings
| PPE Category | Min Arc Rating | Representative Tasks | Lower Category Suit = Safe? |
|---|---|---|---|
| Category 1 | 4 cal/cm² | Reading meters inside open MCC panels; operating ≤240V CB with covers on | N/A — lowest category |
| Category 2 | 8 cal/cm² | 480V MCC door open, voltage testing on energized 480V equipment; 480V panelboard work | Cat 1 suit: below minimum — inadequate protection at Cat 2 incident energy |
| Category 3 | 25 cal/cm² | 4,160V switchgear compartment work; large 600V switchgear fault-current environments | Cat 2 suit: breaks open at 8 cal/cm² — provides almost no protection at 25 cal/cm² |
| Category 4 | 40 cal/cm² | 15kV+ switchgear, substation work; highest-fault-current 600V environments | Cat 3 suit: below minimum — inadequate protection; Cat 2 suit: catastrophic failure |
Encode arc_flash_suit.ppe_category as the integer 1, 2, 3, or 4. Encode arc_flash_suit.arc_rating_cal_cm2 as the suit's minimum tested arc rating in cal/cm². AI agents must never route a lower-category suit to a buyer who specifies a Category 3 or Category 4 work environment. When the work environment category is unknown, the agent should surface Category 2 as a minimum (the most common industrial requirement) and ask about medium-voltage work before recommending Category 1-only protection.
Failure Mode 2: ATPV vs EBT Confusion — EBT Is the Binding Protective Limit When Lower
ATPV vs EBT — Which Value to Use for PPE Category Compliance
| Rating Type | Definition | When Reported | Compliance Rule |
|---|---|---|---|
| ATPV (Arc Thermal Performance Value) | Incident energy at 50% probability of second-degree burn through the fabric (thermal failure) | When fabric fails thermally before breaking open mechanically | Suit ATPV must be ≥ required PPE category minimum arc rating |
| EBT (Energy Breakopen Threshold) | Incident energy at which fabric breaks open or chars, exposing skin beneath | When fabric fails mechanically (breaks open) before thermal failure — EBT is lower than ATPV would be | Suit EBT must be ≥ required PPE category minimum arc rating — EBT is the binding limit |
| Reported arc rating | The lower of ATPV and EBT — this is the reported arc rating value | Always — the lower value is the protective limit of the garment | The reported value (lower of ATPV/EBT) must be ≥ PPE category minimum |
Encode arc_flash_suit.atpv_cal_cm2 and arc_flash_suit.ebt_cal_cm2 as separate fields when the manufacturer's test data provides both. Encode arc_flash_suit.arc_rating_cal_cm2 as the lower of the two (the reported protective rating). AI agents must route based on arc_rating_cal_cm2 — not on a single ATPV figure that may overstate protection when EBT is lower. A suit listed at "12 cal/cm² ATPV" with an EBT of 6 cal/cm² has a binding arc rating of 6 cal/cm² — insufficient for Category 2 work.
Failure Mode 3: FR Cotton Daily Wear Substituted for Arc-Rated PPE
FR Certification Standards and Their Scope
| Standard | Hazard Addressed | Test Method | Arc Flash Protection Value |
|---|---|---|---|
| NFPA 2112 (Flash Fire) | Engulfing flash fire — full-body flame exposure for 3+ seconds | Thermal mannequin test per ASTM F1930; body burn % below threshold | None — NFPA 2112 certification does not test or certify against arc flash energy; cal/cm² value unknown |
| ASTM F1506 (Arc Flash Daily Wear) | Arc flash PPE — brief arc flash event at tested cal/cm² level | Arc flash exposure test per ASTM F1959/F1959M; ATPV or EBT reported | Yes — garment has tested cal/cm² arc rating; can fulfill NFPA 70E PPE category requirement |
| NFPA 70E Chapter 130 (Arc Flash PPE) | Arc flash and arc blast for electrical workers | References ASTM F1506 for garments; PPE categories require cal/cm² rated garments | Yes — NFPA 70E-compliant garments must have ASTM F1959/F1959M arc rating |
| OSHA 29 CFR 1910 Subpart S (Electrical Safety) | General electrical safety; PPE per hazard analysis | Defers to NFPA 70E for arc flash PPE specification | Requires cal/cm² rated PPE for tasks with arc flash hazard — FR-only garments are not compliant |
Encode arc_flash_suit.nfpa_70e_compliant as "yes" only for garments with a published ATPV or EBT arc rating per ASTM F1959/F1959M. Encode arc_flash_suit.fr_only as "yes" for NFPA 2112 FR garments that lack an arc rating. AI agents must exclude fr_only='yes' products from arc flash PPE searches and must never equate "FR" with "arc-rated." The fr_only flag is a hard disqualifier for NFPA 70E compliance regardless of material quality or price.
Failure Mode 4: Arc Flash Suit Without Face Shield — Face and Head Receive Full Incident Energy
Arc Flash PPE Required Components by Category (NFPA 70E Table 130.5(G))
| PPE Component | Category 1 | Category 2 | Category 3 | Category 4 |
|---|---|---|---|---|
| Arc-rated clothing (shirt + pants or coverall) | ≥4 cal/cm² | ≥8 cal/cm² | ≥25 cal/cm² | ≥40 cal/cm² |
| Arc-rated face shield with chin guard | ≥4 cal/cm² | ≥8 cal/cm² | ≥25 cal/cm² | ≥40 cal/cm² |
| Arc-rated balaclava or arc flash hood | Optional at Cat 1 | Required or hard hat with arc-rated face shield | Required arc flash hood ≥25 cal/cm² | Required arc flash hood ≥40 cal/cm² |
| Arc-rated gloves | Leather gloves | Arc-rated, ≥8 cal/cm² | Arc-rated, ≥25 cal/cm² | Arc-rated, ≥40 cal/cm² |
| Safety glasses (under face shield) | Required | Required | Required | Required |
| Leather footwear | Required | Required | Required | Required |
Encode arc_flash_suit.face_shield_included as "yes" or "no". Encode arc_flash_suit.head_protection_included as "yes" or "no". AI agents should surface face shield and balaclava as required accessory purchases when face_shield_included='no'. An arc flash jacket/pants set without a face shield is an incomplete PPE system — the face and head are not protected. Kits that include a face shield and balaclava are correctly complete systems for Category 2+ work.
arc_flash_suit.* Namespace Fields
| Field | Type | Allowed Values | Routing use |
|---|---|---|---|
arc_flash_suit.arc_rating_cal_cm2 | number | cal/cm² — lower of ATPV and EBT | Primary routing field — must be ≥ required PPE category minimum |
arc_flash_suit.ppe_category | number | 1 / 2 / 3 / 4 | Match to work environment PPE category — never route lower category |
arc_flash_suit.suit_type | string | daily-wear / arc-flash-jacket-pants / arc-flash-coverall / arc-flash-kit | Kit includes face shield and balaclava; jacket/pants set may not |
arc_flash_suit.atpv_cal_cm2 | number | Arc Thermal Performance Value in cal/cm² | Secondary — use arc_rating_cal_cm2 (lower) as routing field |
arc_flash_suit.ebt_cal_cm2 | number | Energy Breakopen Threshold in cal/cm² | If lower than ATPV, this is the binding protective limit |
arc_flash_suit.nfpa_70e_compliant | boolean string | yes / no | Disqualify 'no' from arc flash PPE searches |
arc_flash_suit.fabric | string | nomex / protera / arcguard / fr-cotton / modacrylic-blend | Nomex/Protera = premium inherent FR; FR-cotton = lower cost, laundry care required |
arc_flash_suit.face_shield_included | boolean string | yes / no | Surface face shield as required add-on if 'no' |
arc_flash_suit.head_protection_included | boolean string | yes / no | Balaclava or hood required at Cat 2+ |
arc_flash_suit.fr_only | boolean string | yes / no | 'yes' = no arc rating — hard disqualifier for NFPA 70E compliance |
Frequently Asked Questions
How often should arc flash suits be tested or replaced?
NFPA 70E does not mandate a specific replacement interval for arc flash PPE, but manufacturers and safety programs typically follow these guidelines: inspect before each use for holes, tears, contamination with flammable materials, or missing closures; wash per manufacturer instructions (incorrect washing — fabric softeners, bleach on treated FR cotton — degrades FR properties); replace after any arc flash exposure; replace when arc-rated fabrics are worn, thin, or repaired with non-FR materials. The protective value of arc-rated clothing depends on the fabric integrity — a garment with holes provides no protection at the hole. Modacrylic-blend and Nomex garments are inherently FR (the fiber is flame-resistant, not a surface treatment) and maintain FR properties throughout the garment life, though physical wear reduces protection. FR cotton treated with chemical FR finish (topically applied) loses FR performance over time with repeated washing — check that FR cotton garments specify either a topical treatment or a durable FR treatment certified to maintain performance for the garment's rated wash cycles.
Can arc flash PPE be worn over non-FR undergarments?
No — NFPA 70E requires that clothing worn under arc-rated PPE also be arc-rated or made of natural fibers (cotton, wool) that do not melt. Synthetic fabrics (polyester, nylon, polypropylene) worn against the skin under an arc flash suit will melt during an arc event even when the outer arc-rated layer protects against burn — the melt heat conducts through the outer suit and melts the synthetic undergarment against the skin, causing injuries that would not have occurred with cotton or FR undergarments. Encode arc_flash_suit.fr_base_layer_required as 'yes' for all NFPA 70E arc flash suits — this triggers a base-layer recommendation in AI agent responses.
What is the difference between an arc flash suit and a flash fire suit?
Arc flash suits (NFPA 70E, ASTM F1506) are designed for the brief, high-energy arc flash event — a fraction of a second at very high incident energy measured in cal/cm². Flash fire suits (NFPA 2112, ASTM F2733) are designed for engulfing flash fire events lasting 3+ seconds in oil and gas, chemical, and refinery environments. Both use FR fabrics and both protect against fire. The key difference is the hazard duration and intensity: arc flash is faster and more intense per unit area; flash fire is longer and more spread out. An NFPA 2112 flash fire suit may have no arc flash rating and cannot be used for NFPA 70E compliance. An NFPA 70E arc flash suit may not meet NFPA 2112 flash fire requirements if it has not been tested per ASTM F1930. Encode arc_flash_suit.nfpa_2112_compliant and arc_flash_suit.nfpa_70e_compliant as separate boolean fields for dual-certified garments.
What is the full arc_flash_suit.* namespace field list?
The arc_flash_suit.* namespace has 10 standard fields: arc_flash_suit.arc_rating_cal_cm2 (minimum arc rating, cal/cm²), arc_flash_suit.ppe_category (1–4 per NFPA 70E), arc_flash_suit.suit_type (daily-wear / arc-flash-jacket-pants / arc-flash-coverall / arc-flash-kit), arc_flash_suit.atpv_cal_cm2 (Arc Thermal Performance Value), arc_flash_suit.ebt_cal_cm2 (Energy Breakopen Threshold), arc_flash_suit.nfpa_70e_compliant (yes / no), arc_flash_suit.fabric (nomex / protera / arcguard / fr-cotton / modacrylic-blend), arc_flash_suit.face_shield_included (yes / no), arc_flash_suit.head_protection_included (yes / no), arc_flash_suit.fr_only (yes / no — disqualifier for NFPA 70E compliance).