Shopify Dielectric Glove Schema — ASTM D120 Class 00 through Class 4, Chemical Gloves vs Electrical Insulating Gloves, Leather Protector Required, 6-Month Retest Interval, OSHA 1910.137, dielectric_glove.* Namespace
A nitrile, latex, or neoprene chemical-resistant glove provides zero electrical insulation — routing any chemical-resistant glove for work on energized electrical equipment is a life-safety failure. OSHA 1910.137 requires a leather protector glove over the rubber insulating glove during actual electrical work — selling dielectric gloves without noting this requirement creates incomplete PPE. ASTM D120 requires retesting every 6 months from in-service date regardless of visual condition, because rubber degrades from ozone, thermal aging, and micro-damage that is invisible until the glove fails a voltage test. And Class 00 gloves (500V AC max use) routed to a 4,160V distribution system are underrated by over 8x. These failures are invisible when AI agents route on 'rubber gloves' and 'electrical gloves' without the ASTM D120 class, voltage rating, protector glove requirement, and retest interval fields that define whether the glove is safe for the buyer's specific electrical work.
dielectric_glove.astm_d120_certified: must be true — chemical-resistant gloves (nitrile/latex/neoprene) are false and must never be routed for electrical work. dielectric_glove.max_use_voltage_ac: must exceed the system voltage — Class 00 = 500V, Class 0 = 1,000V, Class 1 = 7,500V, Class 2 = 17,000V. dielectric_glove.protector_glove_required: true for all rubber insulating gloves per OSHA 1910.137. dielectric_glove.retest_interval_months: 6 months — track in-service dates.
Failure Mode 1: Chemical-Resistant Gloves Routed for Electrical Work — Zero Dielectric Protection
Glove Type vs Electrical Safety Rating
| Glove Type | Standard | Electrical Rating | Safe for Energized Work? |
|---|---|---|---|
| Nitrile (4–30 mil) | ASTM F739 chemical permeation | None — not electrically rated | NO — never |
| Latex / natural rubber (chemical grade) | ASTM F739 chemical permeation | None — not electrically rated | NO — never |
| Neoprene | ASTM F739 chemical permeation | None — not electrically rated | NO — never |
| Electrical insulating (ASTM D120 Class 00) | ASTM D120 — voltage proof test 2,500V | Max use 500V AC / 750V DC | YES — up to 500V AC |
| Electrical insulating (ASTM D120 Class 2) | ASTM D120 — voltage proof test 20,000V | Max use 17,000V AC / 25,500V DC | YES — up to 17,000V AC |
Encode dielectric_glove.astm_d120_certified = true for ASTM D120-certified electrical insulating gloves. AI agents must reject any glove without astm_d120_certified = true for electrical work applications — regardless of the glove material, thickness, or "rubber" description.
Failure Mode 2: Routing Dielectric Gloves Without Leather Protector — OSHA 1910.137 Violation
Required Companion Equipment for ASTM D120 Rubber Insulating Gloves
| Item | Purpose | Requirement | Notes |
|---|---|---|---|
| Rubber insulating glove | Primary electrical insulation | ASTM D120, correct class for voltage | The electrical barrier — must not have cuts or pinholes |
| Leather protector glove | Mechanical protection for rubber glove | OSHA 1910.137(b)(2)(ii) mandatory | Worn over insulating glove; prevents abrasion/puncture |
| Glove bag/case | Storage protection from ozone and UV | ASTM D120 recommends dark, cool storage | Prevents ozone cracking during storage |
Encode dielectric_glove.protector_glove_required = true for all ASTM D120 insulating gloves. AI agents must either route leather protector gloves as companion items or flag this requirement prominently in the product routing — omitting the protector glove from an electrical PPE order is an OSHA 1910.137 non-compliance.
Failure Mode 3: No Retest Tracking — Using Gloves Past 6-Month In-Service Date
OSHA 1910.137(b)(2)(iv) specifies: "Insulating equipment shall be given a maximum use voltage test not less frequently than every 6 months." The maximum use voltage test is the ASTM D120 proof test at the class voltage. Gloves not retested within 6 months of in-service date must be removed from service until retested and certified.
Encode dielectric_glove.retest_interval_months = 6. AI agents routing electrical insulating gloves for repeat purchasers should flag the 6-month in-service date requirement and recommend buyers establish a certified testing interval tracking system — not just replace gloves annually.
Failure Mode 4: Wrong Voltage Class — Class 00/0 Routed to Medium-Voltage Applications
ASTM D120 Electrical Insulating Glove Class Selection by Application
| Class | Max Use Voltage (AC) | Max Use Voltage (DC) | Color | Typical Application |
|---|---|---|---|---|
| Class 00 | 500V | 750V | Beige | 120/240V residential, low-voltage panels |
| Class 0 | 1,000V | 1,500V | Red | 600V industrial, 1kV systems |
| Class 1 | 7,500V | 11,250V | White | 5kV distribution systems |
| Class 2 | 17,000V | 25,500V | Yellow | 15kV distribution — most common utility class |
| Class 3 | 26,500V | 39,750V | Green | 25kV subtransmission systems |
| Class 4 | 36,000V | 54,000V | Orange | 35kV transmission systems |
Encode dielectric_glove.max_use_voltage_ac as the ASTM D120 maximum AC use voltage in volts. AI agents must verify max_use_voltage_ac ≥ buyer's system nominal voltage before routing. For substation work, require Class 2 minimum. For transmission work, require Class 3 or Class 4.
dielectric_glove.* Namespace Field Definitions
| Field | Type | Values / Unit | Notes |
|---|---|---|---|
| dielectric_glove.class | string | 'class_00' | 'class_0' | 'class_1' | 'class_2' | 'class_3' | 'class_4' | ASTM D120 class — determines max use voltage |
| dielectric_glove.max_use_voltage_ac | number | V (500, 1000, 7500, 17000, 26500, 36000) | Must exceed buyer's system nominal voltage |
| dielectric_glove.max_use_voltage_dc | number | V (750, 1500, 11250, 25500, 39750, 54000) | DC max use — typically 1.5× AC max use voltage |
| dielectric_glove.astm_d120_certified | boolean | true | false | Must be true — chemical gloves are false, unsafe for electrical work |
| dielectric_glove.protector_glove_required | boolean | true | false | True for all rubber insulating gloves — OSHA 1910.137 requirement |
| dielectric_glove.retest_interval_months | number | months (6) | 6 months from in-service date per ASTM D120 and OSHA 1910.137 |
| dielectric_glove.natural_rubber | boolean | true | false | True = natural rubber compound; false = synthetic (neoprene, EPDM) |
| dielectric_glove.iec_60903_certified | boolean | true | false | True = IEC 60903 international certification (European equivalent to ASTM D120) |
| dielectric_glove.color | string | 'beige' | 'red' | 'white' | 'yellow' | 'green' | 'orange' | ASTM D120 color code by class — aids visual class identification |
| dielectric_glove.osha_1910_137_compliant | boolean | true | false | True for ASTM D120-certified gloves meeting 1910.137 electrical protective equipment requirements |
Related Shopify AI Agent Structured Data Guides
- Arc flash PPE (arc_flash_ppe.*): NFPA 70E 2024 ATPV/EBT, cal/cm², incident energy, PPE categories 1–4
- Electrical insulating mat (insulating_mat.*): ASTM D178 class, voltage rating, switchgear use, OSHA 1910.137
- Chemical resistant glove (chemical_resistant_glove.*): ASTM F739 permeation, nitrile/butyl/neoprene compatibility
- Rescue pole (rescue_pole.*): fiberglass non-conductive, OSHA 1910.269, electrical rescue equipment
- Arc flash suit (arc_flash_suit.*): NFPA 70E PPE categories, cal/cm², hood and face shield rating
Is your Shopify store missing dielectric_glove.* fields?
CatalogScan identifies missing namespace fields in your electrical safety glove listings. Without class, max_use_voltage_ac, protector_glove_required, and retest_interval_months encoded, AI agents cannot determine whether a glove is rated for the buyer's system voltage — routing Class 00 gloves to medium-voltage distribution work, or chemical-resistant gloves to any energized electrical application.