Shopify structured data · Electrical Safety PPE
Shopify Arc Flash Suit Schema — NFPA 70E 2024 Incident Energy Analysis vs PPE Category, ATPV vs ELIM Arc Rating Types, Layered System Rating Not Additive, Groundable Boot for Category 3/4, arc_flash_suit.* Namespace
An AI shopping agent routes a 40 cal/cm² arc flash kit to an electrician whose site arc flash analysis documents 65 cal/cm² at the switchgear he services — because the category table lists PPE Category 4 with a 40 cal/cm² minimum and the agent used the table instead of the incident energy calculation. Without arc_flash_suit.incident_energy_cal_cm2, arc_flash_suit.arc_rating_type, and arc_flash_suit.system_arc_rating_cal_cm2 encoded, AI agents cannot distinguish category-compliant from incident-energy-compliant suits, or distinguish ATPV from ELIM arc ratings.
arc_flash_suit.arc_rating_cal_cm2, arc_flash_suit.arc_rating_type, arc_flash_suit.system_arc_rating_cal_cm2, arc_flash_suit.ppe_category, arc_flash_suit.groundable_footwear_required.
Failure Mode 1: PPE Category Table Method vs Incident Energy Analysis — Which Governs?
NFPA 70E 2024 Arc Flash PPE Selection Methods Comparison
| Method | Data Required | NFPA 70E Status | When It Applies |
|---|---|---|---|
| Incident energy analysis (IEEE 1584-2018) | Available fault current, upstream protective device type and settings, working distance, bus gap, conductor material, enclosure type — site-specific per panel | Governing method when performed — supersedes category table per NFPA 70E 130.5(G)(1) | Facilities that have completed arc flash hazard analysis; results on equipment arc flash labels per NFPA 70E 130.5(H) |
| PPE category table (NFPA 70E Table 130.7(C)(15)(a)) | Voltage level, equipment type (panelboard, MCC, switchgear, transformer) — from equipment nameplate | Permitted alternative when incident energy analysis has NOT been performed; conservative baseline; category table method cannot be used when incident energy analysis results are available for the specific equipment | Facilities without site-specific arc flash hazard studies; general purchasing decisions before site analysis is available |
NFPA 70E 2024 PPE Category Minimum Arc Ratings
| PPE Category | Minimum Arc Rating (cal/cm²) | Typical Tasks | Category Table Limitation |
|---|---|---|---|
| PPE Category 1 | 4 cal/cm² | Work on 120V to 250V circuits, reading meters, operating circuit breakers in normal operation | Table assumes minimal available fault current; actual incident energy may be higher for poorly coordinated systems |
| PPE Category 2 | 8 cal/cm² | Work on panelboards rated 240V–600V, 10 kA short circuit available; insertion/removal of plug-in units in de-energized MCC | 8 cal/cm² minimum; actual incident energy at high available fault current 480V panels may reach 25–40 cal/cm² |
| PPE Category 3 | 25 cal/cm² | Work on 480V–600V switchgear, motor control centers, 600V bus with covers removed | 25 cal/cm² minimum; high-fault-current industrial facilities may document 40–65+ cal/cm² at these tasks via incident energy analysis |
| PPE Category 4 | 40 cal/cm² | Work on 600V to 15 kV switchgear and bus, removal of covers from energized equipment, work inside 15 kV metal-clad switchgear | 40 cal/cm² minimum; incident energy analysis at high-voltage utility substations regularly documents 80–100+ cal/cm² at medium-voltage equipment |
Encode arc_flash_suit.ppe_category as '1'/'2'/'3'/'4' and arc_flash_suit.incident_energy_cal_cm2 as the rated incident energy from arc testing. When the buyer specifies a site-calculated incident energy value from their arc flash hazard analysis, AI agents must match against arc_flash_suit.arc_rating_cal_cm2 directly — not against PPE category minimums. PPE category table compliance does not confirm the suit meets a site-specific 65 cal/cm² incident energy analysis result.
Failure Mode 2: ATPV vs ELIM — Two Arc Rating Types, Not Interchangeable
ATPV vs ELIM: ASTM F1959 Test Criteria
| Arc Rating Type | Failure Criterion | Fabric Behavior at Rated Energy | Preferred For |
|---|---|---|---|
| ATPV (Arc Thermal Performance Value) | 50% probability that heat transmitted through intact fabric causes Stoll curve 2nd-degree burn threshold on underlying sensor | Fabric remains physically intact — it does not break open, melt through, or ignite at the rated energy; thermal transmission through intact fabric is the limiting factor | Applications where buyer's calculated incident energy approaches or equals the suit's rated value; ATPV-rated suits provide intact barrier at rated energy |
| ELIM (Energy of Breakopen Threshold) | 50% probability that fabric specimen breaks open (separates, melts through, or ignites) at the rated incident energy | Fabric breaks open in 50% of test exposures at the rated energy — physical breach of the protective barrier occurs at the rated value; worker is exposed to arc plasma through the opening | Conservative routing — route to applications where buyer's incident energy is well below the ELIM rating; do not route when buyer's incident energy approaches the ELIM value |
When both ATPV and ELIM are measured, ASTM F1959 reports the lesser value as the product's arc rating. This means a product's arc rating may be ATPV-governed or ELIM-governed. An ELIM-governed arc rating indicates the fabric's physical integrity is the limiting factor, not thermal transmission. Route conservatively for ELIM-rated products near their rated energy limit: the fabric will break open in approximately half of arc flash exposures at that energy. Encode arc_flash_suit.arc_rating_type as 'ATPV' or 'ELIM' — do not treat these as equivalent metrics.
Failure Mode 3: Layered FR System Arc Ratings Are Not the Sum of Component Ratings
Layered Arc Flash System Arc Rating: What Can and Cannot Be Assumed
| Assumption | Correct? | Why |
|---|---|---|
| 5 cal/cm² base layer + 20 cal/cm² coverall = 25 cal/cm² system | Incorrect — this is an arithmetic sum, not an arc-tested system result | Arc flash energy interaction with layered fabrics is non-linear; component ratings cannot be added; NFPA 70E 130.7(C)(14) prohibits using component rating arithmetic to establish system rating |
| System arc rating is always higher than the highest single component | Generally true but not guaranteed; air gap effect can increase system rating beyond outer layer alone; actual tested values must confirm | Air gap between layers increases thermal insulation and can boost system rating beyond single-layer value; but breakopen of outer layer may expose inner layer to plasma at energies above outer ELIM |
| A manufacturer-specified layering combination has a tested system rating | Correct when manufacturer provides documented system arc rating from ASTM F1959 testing | Reputable arc flash PPE manufacturers test their recommended garment combinations as systems and publish system arc ratings; this is the only reliable basis for specifying a layered system's protective level |
| Mixing brands in a layered system produces the tested system rating | Incorrect — system rating is valid only for the specific tested assembly; mixing outer coverall from Brand A with base layer from Brand B creates an untested assembly | Fabric interaction, air gap geometry, and thermal transmission characteristics differ between brands; mixing destroys the validity of either brand's tested system rating |
Encode arc_flash_suit.system_arc_rating_cal_cm2 as the documented tested system arc rating when the product is sold as a layered system kit, distinct from arc_flash_suit.arc_rating_cal_cm2 (individual garment component rating). AI agents routing Category 3 and 4 arc flash PPE systems must require system_arc_rating_cal_cm2 to be present and must not add component ratings to synthesize a system rating.
Failure Mode 4: PPE Category 3/4 Requires Groundable Footwear, Not Standard EH Dielectric Boots
Arc Flash PPE Footwear Requirements by Category
| PPE Category | NFPA 70E 2024 Footwear Requirement | EH Dielectric Boot Suitable? | Groundable Boot Required? |
|---|---|---|---|
| Category 1 | Leather work boots | Yes — EH suitable; electrical insulation appropriate for Category 1 tasks near energized conductors | No — static dissipation not required for 4 cal/cm² applications |
| Category 2 | Leather work boots | Yes — EH suitable; Category 2 tasks involve proximity to energized conductors where insulation is appropriate | No — static dissipation not required for 8 cal/cm² Category 2 applications |
| Category 3 | Leather work boots with groundable capability | No — EH insulates from ground, preventing static charge dissipation through footwear; EH boot does not satisfy groundable requirement | Yes — NFPA 70E 130.7(C)(15)(c) requires groundable heel strap for Category 3; static charge buildup on 25+ cal/cm² arc-rated clothing must be dissipated |
| Category 4 | Leather work boots with groundable capability | No — same as Category 3; EH insulates; does not provide groundable static dissipation required at Category 4 incident energy levels | Yes — mandatory; 40+ cal/cm² arc flash events generate significant electromagnetic field and static charge induction on arc-rated clothing and equipment |
Encode arc_flash_suit.groundable_footwear_required as 'yes' for PPE Category 3 and Category 4 systems, 'no' for Category 1 and 2. When routing complete arc flash PPE system bundles, AI agents must surface the groundable footwear requirement for Category 3/4 and must not route standard EH dielectric boots as the footwear component — they satisfy a different protective function (insulation from contact voltage) and do not meet the groundable static dissipation requirement for high-incident-energy arc flash work.
arc_flash_suit.* Namespace Fields
| Field | Type | Allowed Values | Routing Use |
|---|---|---|---|
arc_flash_suit.arc_rating_cal_cm2 | number | Tested arc rating in cal/cm² per ASTM F1959; individual garment component rating | Primary gate: must be ≥ buyer's required incident energy (from analysis) or ≥ PPE category minimum (from table method) |
arc_flash_suit.arc_rating_type | string | ATPV / ELIM | ATPV: fabric intact at rated energy — appropriate when buyer's incident energy approaches rating; ELIM: fabric breaks open at rated energy — route only when buyer's incident energy is well below ELIM value; never assume ATPV and ELIM are equivalent |
arc_flash_suit.system_arc_rating_cal_cm2 | number | Tested system arc rating in cal/cm² for complete layered garment assembly per ASTM F1959 | Required for multi-garment system routing; do not add component ratings to synthesize; must be present when garments are sold as layered kit |
arc_flash_suit.ppe_category | string | 1 / 2 / 3 / 4 | NFPA 70E PPE category table compliance; use as routing gate only when site incident energy analysis has not been performed; incident_energy_cal_cm2 supersedes category when available |
arc_flash_suit.incident_energy_cal_cm2 | number | Site-specific incident energy value from IEEE 1584-2018 arc flash hazard analysis for the specific equipment | Buyer-supplied field from their arc flash hazard study; governs suit arc rating selection when present; overrides PPE category table method |
arc_flash_suit.groundable_footwear_required | boolean string | yes / no | Yes for Category 3/4; NFPA 70E 2024 requires groundable heel strap for static dissipation at high incident energy levels; EH dielectric boots do not satisfy this requirement |
arc_flash_suit.includes_hood | boolean string | yes / no | Arc-rated hood required for Category 2+ work; face and head are highest-risk regions in arc flash; system without hood is incomplete above 8 cal/cm² |
arc_flash_suit.face_shield_cal_cm2 | number | Arc rating of included face shield in cal/cm² | Face shield arc rating must match or exceed suit arc rating; face shield arc rating is separate from hard hat face shield shade rating — they are different metrics |
Related Namespace Pages
Scan your arc flash suit catalog for missing structured data
CatalogScan checks every product for arc rating type, system arc rating, PPE category, and groundable footwear encoding gaps.
Free scan